Item: Air Heat Recovery Unit

Short Description: A smart device that can recovery hot energy in the drain air.It is always installed between air ducts.When indoor hot air drain out and outdoor fresh air extract in,the two temperatured air exchange hot in this unit.Finally,the hot is drawn into the fresh air,and heat the fresh air.It help you to save energy consumption,is a self-pay product.

Models & Sizes: See below.

Place of origin: China , Sell to worldwide.

Interested in “Air Heat Recovery Unit”? Order it!
Models & Details for “Air Heat Recovery Unit”

AHE-15

Name:AHE-15WBM AHE-20WBM AHE-25WBM

Main function
●100-250m3/h widely installed in smallapartment,villa and offices.
●Compact super thin design for easier installation and construction space saving
●Super low noise design adopts super low noise ventilator and takes the high efficiency noise-damping technology
●Besides above optional function makes operators use freely
Performance parameter

Model
AHE-15WBM
AHE-20WBM
AHE-25WBM
Power
(V/Hz)
220/50/60
220/50/60
220/50/60
Volume
(m3/h)
150/110
200/150
250/200
Static pressure
(Pa)
100/60
90/60
85/65
Heat recovery rate
(%)
65/68
65/68
65/68
Rated power
(w)
50/45
66/60
75/65
Noise
(dB(A))
38/32
39/32
40/33
Weight
(Kg)
17
17
18
Carton size
(mm)
805*650*275
805*650*275
805*650*275

Dimension diagram

AHE-15-1

Appearance&installation(mm)

A
B
C
D
E
F
G
H
I
φd

495

588
453
500
746
250
15
200
580
100

 


AHE-15b

Name:AHE-15WB AHE-20WB

Main function
●100-200m3/h widely installed in smallapartment,villa and offices.
●Compact super thin design for easier installation and construction space saving
●Super low noise design adopts super low noise ventilator and takes the high efficiency noise-damping technology
●Besides above optional function makes operators use freely
Performance parameter

Model
AHE-15WBM
AHE-20WBM
Power
(V/Hz)
220/50/60
220/50/60
Volume
(m3/h)
150/110
200/150
Static pressure
(Pa)
100/60
90/55
Heat recovery rate
(%)
65/68
60/63
Rated power
(w)
60/50
68/52
Noise
(dB(A))
38/32
39/32
Weight
(Kg)
19
19.5
Carton size
(mm)
805*575*315
805*575*315

Dimension diagram
AHE-15b-1
Appearance&installation(mm)

A
B
C
D
E
F
G
H
I
φd

421

588
463
500
746
240
29
240
507
100

 


AHE-25

Name:AHE-25W AHE-35W…

Main function
●250-1000m3/h widely installed in commercial building hotel poker and chess room,hospital etc.
●Compact super thin design for easier installation and construction space saving
●Super low noise design adopts super low noise ventilator and takes the high efficiency noise-damping technology
●Besides above optional function makes operators use freely
●Panasonic brushless DC motor adopted lower noise super energy saving saving complex energy up to 50% High performance.
(D series dc inverter)
●Optional indoor temperature and carbon dioxide concentration sensor more healthy and more automatically.(D series dc inverter)
Dimension diagram

Model A B C D E F G H I φd
AHE-25W1 670 750 720 680 940 342 112 270 784 150
AHE-35W1 670 750 720 680 940 342 112 270 784 150
AHE-25W 670 885 720 815 1075 342 112 270 784 150
AHE-35W 810 885 860 815 1075 482 112 270 924 150
AHE-40W 810 885 860 815 1075 482 112 270 924 150
AHE-50W 997 966 1045 905 1130 728 38 312 1106 200
AHE-60W 997 966 1045 905 1130 728 38 312 1106 200
AHE-80W 885 1322 936 1252 1488 430 172 396 995 250
AHE-100W 1132 1322 1186 1252 1488 681 172 396 1246 250
AHE-25W/D 670 885 720 815 1075 342 112 270 784 150
AHE-35W/D 810 885 860 815 1075 482 112 270 924 150
AHE-50W/D 997 966 1045 905 1130 728 38 312 1106 200
AHE-80W/D 885 1322 936 1252 1488 430 172 396 995 250
AHE-100W/D 1132 1322 1186 1252 1488 681 172 396 1246 250

AHE-25-1

Performance parameter

Model AHE-25W1 AHE-35W1 AHE-25W AHE-35W AHE-40W AHE-50W AHE-60W
Power (V/Hz) 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60
Volume (m3/h) 250/250/160 350/350/270 250/250/160 350/350/270 400/350/270 500/500/360 600/500360
Static pressure (Pa) 85/65/30 90/60/30 85/65/30 90/60/30 90/60/30 100/60/30 100/60/30
Heat recovery rate (%) 70/70/74 70/70/74 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75
Rated power (w) 105/100/80 140/125/115 105/100/80 140/125/115 150/132/119 190/175/150 215/193/165
Noise (dB(A)) 35/33/31 36/34/31 35/33/31 36/34/31 37/35/32 38/35/32 39/36/32
Weight (Kg) 20 21 23 38.5 39 50 51
Carton size (mm) 1015*830* 1015*830* 1125*830* 1125*985* 1125*985* 1190*1150* 1190*1150
355 355 345 345 345 386 *386

 

Model AHE-80W AHE-100W AHE-25W/D AHE-35W/D AHE-50W/D AHE-80W/D AHE-100W/D
Power (V/Hz) 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60
Volume (m3/h) 800/800/625 1000/780/650 250/250/160 350/350/270 500/500/360 800/800/625 1000/780/650
Static pressure (Pa) 150/100/40 150/100/40 85/65/30 90/60/30 100/60/30 150/100/40 150/100/40
Heat recovery rate (%) 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75
Rated power (w) 320/273/205 450/375/330 70/50/25 85/55/30 133/100/60 220/190/110 300/260/160
Noise (dB(A)) 41/37/33 41/37/33 35/33/31 36/34/31 38/35/32 41/37/33 41/37/33
Weight (Kg) 74 87 22 38 48 72 85
Carton size (mm) 1545*1045* 1545*1300* 1125*830* 1125*985* 1190*1150* 1545*1045* 1545*1300*
470 470 345 345 386 470 470

 


AHE-25

Name:AHE-50W AHE-60W …..

Main function
●250-1000m3/h widely installed in commercial building hotel poker and chess room,hospital etc.
●Compact super thin design for easier installation and construction space saving
●Super low noise design adopts super low noise ventilator and takes the high efficiency noise-damping technology
●Besides above optional function makes operators use freely
●Panasonic brushless DC motor adopted lower noise super energy saving saving complex energy up to 50% High performance.
(D series dc inverter)
●Optional indoor temperature and carbon dioxide concentration sensor more healthy and more automatically.(D series dc inverter)
Dimension diagram

Model A B C D E F G H I φd
AHE-25W1 670 750 720 680 940 342 112 270 784 150
AHE-35W1 670 750 720 680 940 342 112 270 784 150
AHE-25W 670 885 720 815 1075 342 112 270 784 150
AHE-35W 810 885 860 815 1075 482 112 270 924 150
AHE-40W 810 885 860 815 1075 482 112 270 924 150
AHE-50W 997 966 1045 905 1130 728 38 312 1106 200
AHE-60W 997 966 1045 905 1130 728 38 312 1106 200
AHE-80W 885 1322 936 1252 1488 430 172 396 995 250
AHE-100W 1132 1322 1186 1252 1488 681 172 396 1246 250
AHE-25W/D 670 885 720 815 1075 342 112 270 784 150
AHE-35W/D 810 885 860 815 1075 482 112 270 924 150
AHE-50W/D 997 966 1045 905 1130 728 38 312 1106 200
AHE-80W/D 885 1322 936 1252 1488 430 172 396 995 250
AHE-100W/D 1132 1322 1186 1252 1488 681 172 396 1246 250

AHE-50-1

Performance parameter

Model AHE-25W1 AHE-35W1 AHE-25W AHE-35W AHE-40W AHE-50W AHE-60W
Power (V/Hz) 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60
Volume (m3/h) 250/250/160 350/350/270 250/250/160 350/350/270 400/350/270 500/500/360 600/500360
Static pressure (Pa) 85/65/30 90/60/30 85/65/30 90/60/30 90/60/30 100/60/30 100/60/30
Heat recovery rate (%) 70/70/74 70/70/74 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75
Rated power (w) 105/100/80 140/125/115 105/100/80 140/125/115 150/132/119 190/175/150 215/193/165
Noise (dB(A)) 35/33/31 36/34/31 35/33/31 36/34/31 37/35/32 38/35/32 39/36/32
Weight (Kg) 20 21 23 38.5 39 50 51
Carton size (mm) 1015*830* 1015*830* 1125*830* 1125*985* 1125*985* 1190*1150* 1190*1150
355 355 345 345 345 386 *386

 

Model AHE-80W AHE-100W AHE-25W/D AHE-35W/D AHE-50W/D AHE-80W/D AHE-100W/D
Power (V/Hz) 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60
Volume (m3/h) 800/800/625 1000/780/650 250/250/160 350/350/270 500/500/360 800/800/625 1000/780/650
Static pressure (Pa) 150/100/40 150/100/40 85/65/30 90/60/30 100/60/30 150/100/40 150/100/40
Heat recovery rate (%) 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75
Rated power (w) 320/273/205 450/375/330 70/50/25 85/55/30 133/100/60 220/190/110 300/260/160
Noise (dB(A)) 41/37/33 41/37/33 35/33/31 36/34/31 38/35/32 41/37/33 41/37/33
Weight (Kg) 74 87 22 38 48 72 85
Carton size (mm) 1545*1045* 1545*1300* 1125*830* 1125*985* 1190*1150* 1545*1045* 1545*1300*
470 470 345 345 386 470 470

 


AHE-80

 

Name:AHE-80W AHE-100W ….

Main function
●250-1000m3/h widely installed in commercial building hotel poker and chess room,hospital etc.
●Compact super thin design for easier installation and construction space saving
●Super low noise design adopts super low noise ventilator and takes the high efficiency noise-damping technology
●Besides above optional function makes operators use freely
●Panasonic brushless DC motor adopted lower noise super energy saving saving complex energy up to 50% High performance.
(D series dc inverter)
●Optional indoor temperature and carbon dioxide concentration sensor more healthy and more automatically.(D series dc inverter)
Dimension diagram

Model A B C D E F G H I φd
AHE-25W1 670 750 720 680 940 342 112 270 784 150
AHE-35W1 670 750 720 680 940 342 112 270 784 150
AHE-25W 670 885 720 815 1075 342 112 270 784 150
AHE-35W 810 885 860 815 1075 482 112 270 924 150
AHE-40W 810 885 860 815 1075 482 112 270 924 150
AHE-50W 997 966 1045 905 1130 728 38 312 1106 200
AHE-60W 997 966 1045 905 1130 728 38 312 1106 200
AHE-80W 885 1322 936 1252 1488 430 172 396 995 250
AHE-100W 1132 1322 1186 1252 1488 681 172 396 1246 250
AHE-25W/D 670 885 720 815 1075 342 112 270 784 150
AHE-35W/D 810 885 860 815 1075 482 112 270 924 150
AHE-50W/D 997 966 1045 905 1130 728 38 312 1106 200
AHE-80W/D 885 1322 936 1252 1488 430 172 396 995 250
AHE-100W/D 1132 1322 1186 1252 1488 681 172 396 1246 250

AHE--1

Model AHE-25W1 AHE-35W1 AHE-25W AHE-35W AHE-40W AHE-50W AHE-60W
Power (V/Hz) 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60
Volume (m3/h) 250/250/160 350/350/270 250/250/160 350/350/270 400/350/270 500/500/360 600/500360
Static pressure (Pa) 85/65/30 90/60/30 85/65/30 90/60/30 90/60/30 100/60/30 100/60/30
Heat recovery rate (%) 70/70/74 70/70/74 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75
Rated power (w) 105/100/80 140/125/115 105/100/80 140/125/115 150/132/119 190/175/150 215/193/165
Noise (dB(A)) 35/33/31 36/34/31 35/33/31 36/34/31 37/35/32 38/35/32 39/36/32
Weight (Kg) 20 21 23 38.5 39 50 51
Carton size (mm) 1015*830* 1015*830* 1125*830* 1125*985* 1125*985* 1190*1150* 1190*1150
355 355 345 345 345 386 *386

 

Model AHE-80W AHE-100W AHE-25W/D AHE-35W/D AHE-50W/D AHE-80W/D AHE-100W/D
Power (V/Hz) 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60 220/50/60
Volume (m3/h) 800/800/625 1000/780/650 250/250/160 350/350/270 500/500/360 800/800/625 1000/780/650
Static pressure (Pa) 150/100/40 150/100/40 85/65/30 90/60/30 100/60/30 150/100/40 150/100/40
Heat recovery rate (%) 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75 71/71/75
Rated power (w) 320/273/205 450/375/330 70/50/25 85/55/30 133/100/60 220/190/110 300/260/160
Noise (dB(A)) 41/37/33 41/37/33 35/33/31 36/34/31 38/35/32 41/37/33 41/37/33
Weight (Kg) 74 87 22 38 48 72 85
Carton size (mm) 1545*1045* 1545*1300* 1125*830* 1125*985* 1190*1150* 1545*1045* 1545*1300*
470 470 345 345 386 470 470
Buying Guide to “Air Heat Recovery Unit”
  • The Air Heat Recovery Unit is available for retail and wholesale;
  • The place of origin is in China,when you buy one or a small quantity,please consider freight into the cost;
  • Accept bulk order with Container delivery;
  • Accept customized production;
  • More types of  Air Heat Recovery Unit are not displayed on the web.If the item above doesn`t meet your requirement,please contact us to email: [email protected] ,we can supply a favourite item you need.
General Knowledge on “Air Heat Recovery Unit”

Work Principles

Total heat exchanger is an energy-efficient air conditioning and ventilation equipment, its core function is to use the indoor and outdoor air temperature difference and humidity difference, good movement transducer characteristics through energy recovery, displacement ventilation in the two-way, while generating energy exchange enable effective access to fresh air ventilation in the full heat and enthalpy or temperature sensible heat type CHA CHB, thus saving energy consumption of fresh air pretreatment to achieve the purpose of energy saving ventilation, energy saving effect is very significant.

Advantage

High heat efficiency:
The use of advanced structural design countercurrent air heat exchanger in the module time to get longer, and the stripe-shaped ventilation channels has greatly increased the heat transfer area, the heat exchange efficiency is improved by 5% to 10%.

Non-polluting energy recovery:
Total heat type made of nano-porous polymer materials exchanger membrane, thermal moisture permeability good, airtight security, total heat recovery fresh air without pollution. Sensible heat type of high quality aluminum foil, corrosion resistant, high temperature properties, high temperature exchange efficiency.

Compact form factor:
Hexagonal shape reduces the module thickness, special ventilation channels allow the module made shorter than the cross-flow movement.

Long life:
With ABS frame structure, durable, cross-flow movement of life than doubled.

Combination of convenience:
Multiple module combinations, you can choose the best configuration based on the model as needed.

Stable performance, without the need to clean:
Ventilation channel flow line design, can effectively prevent the dust in the early effect of the pre-filter, the heat transfer efficiency can be maintained long-term stability and eliminates the need for periodic cleaning of cross-flow movement of trouble.

Structure
Equipment consists of the chassis, the total heat exchange core and supply and exhaust machine.

Total heat exchange core
Countercurrent structure technology successfully developed a new generation of modular energy recovery movement, compared with the traditional cross-flow heat recovery movement, performance parameters are obtained greatly improved and improved, and in the use of more flexible and convenient.

Higher heat transfer efficiency: the whole heat transfer efficiency increased by 5% -10%.
Smaller dimensions: the overall decline of about 20 percent, saving installation location.
More stable performance: the long-term continuous operating conditions, such as heat transfer efficiency to maintain a stable number of indicators.
More comprehensive models: air flow 100m3 / h-100000m3 / h, sufficient to meet the needs of different users.
Maintenance more convenient: just regular cleaning filters, and energy recovery module without professional clean and make maintenance easier.
Photocatalytic disinfection and purification (optional): the introduction of US Wasun photocatalytic disinfection technologies mature, bacteria, viruses kill rate of 99.9%.
DDC building automation and filter pressure alarm (optional): remote monitoring and automatic alerts cleaning (replacement) filter.
Intelligent controller (optional): imported control unit, on-line detection of the user preset working conditions, intelligent operation.

Selection Guide

Air heat exchanger, heat exchanger solutions, heat exchangers Selection Guide

Room
不吸烟
少量吸烟
大量吸烟
一般病房
体育馆
影剧院  百货商场
办公室
计算机房
餐厅
高级客房
会议室
每人所需新风量Q(m/h)
17-42
8-20
8.5-21
25-62
40-100
20-50
30-75
50-125
房间新风换气次数P(次/h)
1.06-2.65
0.50-1.25
1.06-2.66
1.56-3.90
2.50-6.25
1.25-3.13
1.88-4.69
3.13-7.81

 Calculation example:

Determine when the room needed fresh air, Xiamen Hui conditioning reminder: should be considered based on the number of rooms and interior space staff. Respectively, according to “person needed fresh air,” according to the table data and recommended “room fresh air ventilation rate” calculated fresh air value, whichever is greater, as the basis for the selection of equipment. A computer room area S = 50 (m2), net height h = 3 (m), staff n = 12 (people), if needed fresh air per person basis, to take the necessary fresh air per person q = 50 (m3 / h), the fresh air
Q1 = n · q = 12 × 50 = 600 (m3 / h).
If you press room fresh air ventilation rate is calculated, taking the room fresh air ventilation frequency p = 4.5 (times / h).
The fresh air Q2 = p · s · h = 4.5 × 50 × 3 = 675 (m3 / h).
Because Q2> Q1, so they chose Q2 (ie 675m3 / h) as equipment selection parameter data

HVAC Parts >>Ventilation Material>>Air Heat Recovery Unit

One Inquiry to Air Heat Recovery Unit

  1. Hello! Im looking for electric scheme for your AHE 35w/d recuperator. Where can I get pdf with those informations? Thanks!